Main Specifications
|
---|
Product Description
|
Minuteman - power distribution cabinet - 9000 Watt - 10000 VA
|
Device Type
|
Power distribution cabinet - external
|
Rack Size
|
19" - 42U
|
Weight
|
482.81 lbs
|
Input Wiring
|
1-phase
|
Input Voltage
|
AC 208 - 240 V
|
Output Voltage
|
AC 208/220/230/240 V ± 2%
|
Power Capacity
|
9000 Watt / 10000 VA
|
Input Connectors
|
2 x hardwire, power NEMA L6-30P
|
Output connectors
|
3 x power NEMA L6-30R ¦ 2 x power NEMA L6-20R ¦ 1 x 3 pin terminal block
|
Run Time (Up To)
|
3 min at full load
|
Dimensions (WxDxH)
|
23.6 in x 42.1 in x 78.3 in
|
General
|
---|
Device Type
|
Power distribution cabinet - external
|
Height (Rack Units)
|
42U
|
Rack Size
|
19"
|
Miscellaneous
|
---|
Features
|
Built-in UPS, full-height, powder-coated, steel housing, key lock, vertical orientation, fully assembled, internal cable routing, 4 x adjustable mounting rails, split rear doors, Key-Locking Latch, mesh front door, 180° swing, reversible front door, removable roof panel, pure sinewave output, internal bypass, double conversion, touch screen LCD display
|
Battery
|
---|
Run Time (Up To)
|
3 min at full load ¦ 11 min at half load
|
Power Device
|
---|
UPS Technology
|
On-line
|
Input Voltage
|
AC 208 - 240 V
|
Frequency Provided
|
50/60 Hz ± 0.1%
|
Input Wiring
|
1-phase
|
Frequency Required
|
40 - 70 Hz
|
Input Connectors
|
2 x hardwire, power NEMA L6-30P
|
Power Output Connectors Details
|
3 x power NEMA L6-30R ¦ 2 x power NEMA L6-20R ¦ 1 x 3 pin terminal block
|
Output Voltage
|
AC 208/220/230/240 V ± 2% - 50/60 Hz
|
Max Electric Current
|
32 A
|
Power Capacity
|
9000 Watt / 10000 VA
|
Surge Suppression
|
Yes
|
Surge Energy Rating
|
3.14 Joules
|
Circuit Protection
|
Circuit breaker
|
Power Factor (PF)
|
0.99
|
Total Harmonic Distortion (THD)
|
2 %
|
Dimensions & Weight
|
---|
Width
|
23.6 in
|
Depth
|
42.1 in
|
Height
|
78.3 in
|
Weight
|
482.81 lbs
|